Thinking of self installing a 5kW solution onto a South facing garage. DIY solution appears to be 60% cheaper than hiring a local installer (Ohio)

You are viewing a single thread.
View all comments View context
3 points

Schneider MPPT 150. We sell a lot of Schneider at work and I got a good price on it. However it’s totally a piece of crap. It’s the only “150v” device I’ve ever seen where 150v is the do not exceed voltage rather than the operating voltage, and it will trip offline at 140v which causes a huge issue here in Canada where OCV can rise greatly below -20C.

Wouldn’t recommend Schneider in general as they require their own proprietary CANBus mod to get telemetry out of any of their equipment.

permalink
report
parent
reply
1 point

That’s been my impression of Schneider, great on AC but their solar stuff is a placeholder for “nobody every got fired for buying Schneider”. I thought they ran Modbus on their comms, pretty sure I’ve seen the modbus maps for them around the Homeassistant forums. Maybe it’s just some equipment, but the Conext is modbus afaik.

I wouldn’t say the “150V” should be operating voltage by default, most SCCs I’ve used put that as the “do not exceed” number, just like the current. I’ve smoked relatively expensive charge controllers by being slightly over either of those numbers. Though Victron seem to be able to take it for a while without cratering.

permalink
report
parent
reply
1 point

Conext series support modbus BUT only through an overpriced gateway unit, the actual devices speak Xanbus unless they have updated them. There have been reverse engineering efforts that I think found it to be a polarity flipped or bit flipped CANbus but at the time nobody had a reliable translation layer. I believe Schneider bought Xantrex and rebranded their inverters and chargers as their Conext solar line.

The “do not exceed” nameplate ratings may be more typical in solar, but in the regular electrical world when I buy a solid state device like a 480 volt VFD, I expect it to run at 480VAC, and in fact to have a fairly broad operating range from probably 450-500VAC. Likewise I would expect the current rating to be full load operating current, hopefully with at least a 10% service factor and 20% safety margin on top of that.

I was honestly pretty disappointed when a 150VDC unit tripped offline at 140VDC, not even making the “nameplate rating” but if this is standard for the industry I guess I can’t pick at Schneider for that at least.

permalink
report
parent
reply
1 point

140 is a little light but yah, it’s definitely a solar thing only. It’s possible it bounced over the 150 for a very short time to trip the cutout, and the 140 number you’re seeing is a time-smoothed average in your reporting system. If you’re using something trustworthy like a Smartshunt to get that data, then yah, tripping 10V short isn’t great.

permalink
report
parent
reply

Asklemmy

!asklemmy@lemmy.ml

Create post

A loosely moderated place to ask open-ended questions

Search asklemmy 🔍

If your post meets the following criteria, it’s welcome here!

  1. Open-ended question
  2. Not offensive: at this point, we do not have the bandwidth to moderate overtly political discussions. Assume best intent and be excellent to each other.
  3. Not regarding using or support for Lemmy: context, see the list of support communities and tools for finding communities below
  4. Not ad nauseam inducing: please make sure it is a question that would be new to most members
  5. An actual topic of discussion

Looking for support?

Looking for a community?

Icon by @Double_A@discuss.tchncs.de

Community stats

  • 9.7K

    Monthly active users

  • 5.6K

    Posts

  • 307K

    Comments