So I have a rackmount server with 2 servers connected to it one draws 650w max and the other 400w max. Both have their own ups CYBERPOWER 825AVR, but during a power outage it just shut off. Both are old Ups’s so it seems I need to replace them because the battery doesn’t hold. Also sometime it just seems to shut off and give the long beep even though there was no power outage. Not sure why. Since I have a rackmount server I’m open to buying a rackmount UPS as well but not necessary. What do you recommend? Do I get an Ups for each server separately ?

You are viewing a single thread.
View all comments
1 point

What model and configuration are both of your servers?

permalink
report
reply

Homelab

!homelab@selfhosted.forum

Create post

Rules

  • Be Civil.
  • Post about your homelab, discussion of your homelab, questions you may have, or general discussion about transition your skill from the homelab to the workplace.
  • No memes or potato images.
  • We love detailed homelab builds, especially network diagrams!
  • Report any posts that you feel should be brought to our attention.
  • Please no shitposting or blogspam.
  • No Referral Linking.
  • Keep piracy discussion off of this community

Community stats

  • 9

    Monthly active users

  • 1.4K

    Posts

  • 6K

    Comments