Why yes, that is a natural gas line running to the furnace and water heater: https://www.reddit.com/r/electricians/comments/1fpo26t/not_something_you_see_everyday_evidently_this/

Not something you see everyday. Evidently this image has gone a bit viral, but this is a friend of mines house. She hit me up wondering if I knew what might cause it. The flex was pulling about 175 amps and was at 1200 degrees. There’s to be a whole news story on it and everything.

Mother of god, dare I say this post… blew up. There are a lot of questions and there is no way I can get to everyone. Basically, during a storm a tree fell on the incoming lines and it caused some fucked up high voltage things and created a new ground.

You are viewing a single thread.
View all comments View context
33 points
*

according to that reddit post, during a storm power line fell on gas meter, energizing gas line. now, that means that current flows bypassing meter and breakers entirely, going to ground via gas line, glowing flex, then water pipes and/or neutral. normal breakers won’t trip, because neutral does not have breakers. GFCI should trip, but it does nothing to stop gas pipe from glowing because current that heats it doesn’t flow through there. to unfuck this particular situation you’d need to trip breaker at substation, or disconnect power line going to that area

gas line could be shut off in principle, but it’ll be energized, so it’s not an option

permalink
report
parent
reply
21 points

yikes. worse than I thought

permalink
report
parent
reply
19 points

yeah that’s on the more catastrophic end of scale, nothing can be done at that residential address

permalink
report
parent
reply
6 points

why is the US grid so feeble that leakages of this size (and surely a whole neighborhood’s gas network getting heated to these temperatures is detectable, right?) aren’t automatically disabled by the power company’s computers or some other controllers in the network?

permalink
report
parent
reply

If I didn’t want the house to burn down for the insurance, I’d probably go shoot the power line down. Finally a use for BMG.

permalink
report
parent
reply
11 points
*

that sounds pretty dangerous and i’m not sure if it would even work, because for it to work it requires line to get shorted somewhere else with better ground resistance, tripping breaker at substation. if it fails, you have now high step voltage on the ground and not just near water pipes underground. or it requires line to be cut, and to be sure you’d need to hit all 4 (euro) or 3 (american) wires or insulators. or you could try to pull out fuses at substation, (with insulated tools, on low voltage side) at least for these that i’ve seen it’s possible (like this one https://www.sonepar.fr/catalog/fr-FR/products/05584019458). if fuses are bolted on tho, shit outta luck. (no idea what americans are using)

e: the more i read about american electrical code, the more horrified i get. you can get mains voltages of 120v phase-neutral, 208v phase-neutral, 208v interphase, 230v interphase, 240v interphase, 240v phase-neutral, 277v phase-neutral, perhaps 416v phase-neutral, 480v interphase, or perhaps 480v phase-neutral. of which 277v and 480v are for business customers only? (and 347v, 600v in canada)

this can only be a result of plug manufacturers conspiracy

High-leg delta (also known as wild-leg, stinger leg, bastard leg, high-leg, orange-leg, red-leg, dog-leg delta) is a type of electrical service connection for three-phase electric power installations. It is used when both single and three-phase power is desired to be supplied from a three phase transformer (or transformer bank)

if you want to supply both three-phase and single-phase, supply three-phase as symmetric three-phase + neutral and supply single-phase as phase-to-neutral. it’s simple, it’s sane, it’s standardized, and it’s efficient in copper. that way nobody needs 200A circuits, 7kV transmission line running down every damn street and substation every 5 houses because all high power loads are three-phase, that also means no large imbalances in load happen

it looks like end result of decades of penny pinching managerialism with zero planning for any standardization

permalink
report
parent
reply

… pretty dangerous… better ground resistance, …on the ground and… underground… ,… hit all 4 (euro) or 3 (american) substation,… shit outta luck.

Hamas has opened a new front.

permalink
report
parent
reply
6 points
*

Jeez, sounds like a Roland Emmerich movie.

“Get me the president!”

permalink
report
parent
reply